Категория: Руководства
Degree of protection
IP 21 Floor standing
Power range for 50. 60 Hz line supply (kW/HP)
Three-phase: 200. 240 V (kW/HP)
Three-phase: 380. 440 V (kW/HP)
Three-phase: 380. 480 V (kW/HP)
Variable speed drives Altivar Process. Supply voltage three-phase 200. 240 V 50/60 Hz. THDI y 44% at 100% load in Normal DutyMotor. Power
indicated on
rating plate (2),
ND:
Line supply.
Line current (3)
240V, A
Altivar Process.
Max. transient
current for
60 s, A
(1) Altivar Process ATV630U07M3. D75M3 drives have been designed without an EMC filter. An additional filter can be added to help meet more stringent requirements and reduce electromagnetic emissions.
(2) These values are given for a nominal switching frequency of 4 kHz up to ATV630D22M3, or 2.5 kHz for ATV630D30M3. D75M3 for use in continuous operation. The switching frequency is adjustable from 2. 12 kHz for all ratings. Above 2.5 or 4 kHz (depending on the rating), the drive will automatically reduce the switching frequency in the event of an excessive temperature rise. For continuous operation above the nominal switching frequency, derate the nominal drive current (see the derating curves on our website www.schneider-electric.com ).
(3) Typical value for the indicated motor power and for the maximum prospective line Isc.
(4) Values given for applications requiring a slight overload (up to 110%).
(5) Values given for applications requiring a significant overload (up to 150%).
(6) IP21 / UL Type 1 with additionnal option VW3A9704.Note: Consult the summary tables of possible drive, option, and accessory combinations (see page 60824/2).
Variable speed drives Altivar Process. Supply voltage three-phase 380. 480 V 50/60 Hz. IP 21/UL type 1, 380. 480 V drives with integrated category C2 or C3 EMC filter (6). THDI y 44% at 100% load in Normal DutyMotor.
Power indicated
on rating plate,
ND:
(1) These values are given for a nominal switching frequency of 4 kHz, settable from 2 to 12 kHz up to ATV630D45N4, or 2.5 kHz, settable from 2 to 8 kHz for ATV630D55N4. C16N4 and ATV630C11N4F. C16N4F for use in continuous operation.
Above 2.5 or 4 kHz (depending on the rating), the drive will automatically reduce the switching frequency in the event of an excessive temperature rise. For continuous operation above the nominal switching frequency, derate the nominal drive current (see the derating curves on our website www.schneider-electric.com).
(2) Typical value for the indicated motor power and for the maximum prospective line Isc.
(3) Values given for applications requiring a slight overload (up to 110%).
(4) Values given for applications requiring a significant overload (up to 150%).
(5) IP21 / UL Type 1 with additionnal option VW3A9704.
(6) C2 EMC filter for ATV630U07N4 to ATV630D45N4, C3 EMC filter above ATV630D45N4.
Altivar Process drives can help improve equipment performance and reduce exploitation costs by optimizing energy consumption and user comfort.
They provide integrated safety and automation functions that meet the requirements of the most demanding applications.
They also have various optional communication cards available for seamless integration into the main automation architectures.
Altivar Process drives feature numerous configurable I/O as standard to facilitate adaptation to specific applications.
They offer a plug & play solution, whereby parameters are preset in the factory to the desired configuration, to help save process control and operating time.
Altivar Process is available on wall-mounting IP21/IP55 and on floor standing IP21/IP54.
Altivar Process drives can also be supplied as a customized solution developed by Schneider Electric based on customer specifications.
Altivar Process drives are designed to adapt to significant levels of thermal stress and to the harshest environments.
Altivar Process drives help to optimize power consumption by reducing the rms nput current for the same load.
Depending on the model, Altivar Process drives can also reduce power consumption by up to 60% on each stop by disabling the power section, the fans, the backlight on the graphic display terminal, etc. This "stop and go" function is automatic on each stop and requires no extra investment (no line contactor or 24 V power supply required).
EnvironmentAltivar Process drives have been designed to meet the requirements of environmental protection directives and regulations:
Compliance with electromagnetic compatibility requirements has been incorporated into the design of the drive, which simplifies installation and provides an economical means of helping to ensure equipment meets e marking requirements.
Altivar Process drives have a category C2 or C3 EMC filter, except ATV630U07M3. D75M3 models which can take an additional filter to meet more stringent requirements (see page 60827/6).
Altivar Process drives are ergonomically designed to adapt to any type of installation:
(1) European directive 2002/95/EC Restriction Of Hazardous Substances (applicable in 2016)
(2) European regulation No. 1907/2006
(3) According to IEC 62635 Guidelines
Скачайте опросный лист на подбор и поставку преобразователей частоты ALTIVAR 630 от Schneider Electric (Шнайдер Электрик), заполните и отправьте на email sales@en-el.ru - наши специалисты помогут Вам подобрать оборудование, наиболее полно отвечающего требованиям Вашего предприятия.
Преобразователь частоты Altivar Process предназначен для управления асинхронными и синхронными двигателями мощностью от 0,75 до 315 кВт и напряжением 200, 400, 500, 690 В.
Altivar Process – это первый преобразователь частоты с сервисными функциями мониторинга и диагностики технологического процесса, обладающий большим количеством приложений для водоснабжения и водоотведения, а так же широчайшими коммуникационными и визуализационными возможностями.
Altivar Process имеет специализированные функции для управления насосами.
Altivar Process предоставляет доступ ко всем технологическим переменным, синхронизированным за счет интегрированных в преобразователь часов реального времени. К вашим услугам специализированные функции, такие как stop&go, спящий режим и отображение рабочей точки насоса.
Доступ к информации
С помощью виджетов вы можете легко создать свою приборную панель на экране монитора. Информация доступна в соответствии с правами доступа и безопасности.
Оптимизация энергопотребления может быть достигнута за счет предоставляемых данных об энергопотреблении, оценки энергоэффективности и отслеживания отклонений.
Функции защиты в Altivar Process могут быть легко активированы для включения защит насосной станции. Давление на входе и выходе насоса, расход, температура – любой параметр, влияющий на производительность, может контролироваться.
Altivar Process следит за насосом, обеспечивая безотказную работу на протяжении всего срока службы.
Современные цифровые технологии
Динамическое отслеживание: Встроенные часы позволяют отслеживать все события в реальном времени.
Динамическая поддержка: При помощи динамических QR-кодов теперь намного легче и быстрее получить необходимую информацию для решения возникших проблем.
Цифровой журнал событий: Уникальная функция хранения информации о состоянии вашего преобразователя.
Поддержка партнеров: Наши специалисты помогут вам достичь максимального коэффициента окупаемости инвестиций и оптимизировать эксплуатацию оборудования на протяжении всего срока службы.
Интеграция в решения Schneider Electric
Altivar Process предлагает инновацинную систему контроля и управления технологическими процессами, которая повышает эксплуатационные характеристики вашей установки благодаря:
Быстрой замене: замена вышедшего из строя оборудования менее чем за 3 мин. Задайте имя новому устройству и закачайте сохраненную конфигурацию с FDR-сервера.
Передаче данных: копирование, дублирование и обновление вашей конфигурации с ПЛК.
Полной интеграции в вашу автоматизированную систему управления и прозрачному доступу к данным, облегчающему вашу жизнь.
Преобразователи Altivar Process располагают шестью дискретными и тремя аналоговыми входами, двумя аналоговыми и тремя релейными выходами.
Преобразователи Altivar Process имеют встроенные коммуникационные протоколы Modbus/TCP, Modbus serial link.